Whole House Standby Generator kW Sizing Calculator

Size a home standby generator from your central AC, well pump, water heater and sump pump: running watts plus the largest motor start, rounded to a standard size.

Free · No sign-up · Last reviewed

Quick start:

Your project size

Recommended Generator Size

18 kW Standby Generator Needed: 14.8 kW (running + largest start)

Running Load & Largest Motor Start

7.3 kW running | +7.5 kW starting 4-ton central AC

Want a real price for this whole hou e standby generator kw sizing calculator project?

Get up to 3 free quotes from local contractors. No obligation. Your numbers are included.

Materials list

MaterialQuantityUnitNotes
Home Standby Generator (18 kW)1UnitNatural gas or propane
Automatic Transfer Switch1SwitchSized to your service; whole-house or essential circuits
Concrete or Composite Mounting Pad1PadPlacement per the manufacturer's clearance rules
Refrigerator700 Wrunning+700 W to start
Furnace blower / air handler800 Wrunning+400 W to start
Lights, outlets & electronics (our allowance)1,000 Wrunningno motor start
4-ton central AC4,800 Wrunning+7,500 W to start

Estimated cost: DIY vs. contractor

National Average
DIY Raw Materials Only
$4,860 – $6,980

Cost of raw lumber, concrete, shingles, wire, or stone without equipment rentals or labor.

Hired contractor
$10,840 – $15,640

Full installation: permits, site prep, skilled trade labor, equipment, and structural warranty.

Estimated Sweat Equity
~$7,320

Average trade labor savings if executed as a skilled DIY homeowner project.

Running Load + Largest Motor Start

Rendering formula...

Generator Sizing for 4 Loads

  1. Running watts: Refrigerator 700 + Furnace blower / air handler 800 + Lights, outlets & electronics (our allowance) 1,000 + 4-ton central AC 4,800 = 7,300 W.
  2. Largest single motor start: 4-ton central AC, +7,500 W.
  3. Needed = 7,300 + 7,500 = 14,800 W (Generac's method: all running watts plus the biggest starting burst).
  4. Smallest common standby size that covers it: 18 kW.
Tip: Air conditioner starting draw varies a lot between models. Check the nameplate (locked-rotor amps), and ask the installer about a soft starter or load management, which can let a smaller generator run the AC.

Quick Reference Sizing & Coverage Table

Standard commercial specifications and pre-calculated project benchmarks.

Home SetupRunning LoadLargest StartNeededGenerator Size
No central AC, gas water heater2.5 kW0.7 kW (fridge)3.2 kW10 kW
3-ton AC, gas water heater6.1 kW6.0 kW (AC)12.1 kW14 kW
4-ton AC, 1 HP well, sump pump9.8 kW7.5 kW (AC)17.4 kW18 kW
5-ton AC, electric water heater13.0 kW9.0 kW (AC)22.0 kW22 kW
Generac sizing method; supplier appliance load chart

Have the Installer Confirm the Load

The calculator adds the running watts of your main loads and the single largest motor start. Real AC starting draw varies by model, so check the nameplate. A generator must connect through a transfer switch, never by back-feeding an outlet, and placement must follow the manufacturer's clearances and local code.

Frequently Asked Questions

What size generator do I need for a house with central air?

Add the running watts of everything that may run at once, then add the biggest motor's starting surge. With a 3-ton AC and a gas water heater, that's about 12 kW, so a 14 kW standby unit; a 5-ton AC with an electric water heater comes to about 22 kW.

Why does the AC matter so much for generator size?

Compressor motors draw several times their running power for a moment when they start. The generator has to supply that burst on top of everything else that's running.

Can a soft starter let me use a smaller generator?

A soft starter reduces the AC's starting surge, which can let a smaller generator start it. How much it helps depends on the product and the compressor, so ask your installer to check against the generator's surge rating.

What is load management?

A load management device keeps big loads, like the AC or an electric water heater, from starting at the same time, so a smaller generator can run the house. Many automatic transfer switches offer it.