100 Amp Subpanel Wire Size Calculator

For a 100 amp subpanel 100 ft away, 1 AWG aluminum or 3 AWG copper keeps voltage drop near 2% at the full 100 amps. Past about 140 ft, both need to go up a size. Enter your distance and the calculator does the voltage-drop math.

Free · No sign-up · Last reviewed

Quick start:

Your project size

(ft)
ft

Recommended 100A Feeder Wire

1 AWG Aluminum 4-Conductor Feed (2 Hot, 1 Neutral, 1 Ground)

Voltage Drop at 100 A

1.58% over 75 ft

Want a real price for this 100 amp subpanel wire size calculator project?

Get up to 3 free quotes from local contractors. No obligation. Your numbers are included.

Materials list

MaterialQuantityUnitNotes
Feeder Cable or Conductors (1 AWG Aluminum)85Feet2 insulated hots, insulated neutral and equipment ground
100-Amp 240V Main Lug Subpanel with Separate Ground Bar1PanelNeutral and ground kept separate in a subpanel
Schedule 40 PVC Conduit (size from the conduit fill tables for your wire type)75FeetFor underground or exposed runs
Grounding Electrode (if the subpanel is in a detached building)1SystemAsk your inspector what your jurisdiction requires

Estimated cost: DIY vs. contractor

National Average
DIY Raw Materials Only
$618 – $908

Cost of raw lumber, concrete, shingles, wire, or stone without equipment rentals or labor.

Hired contractor
$1,525 – $2,375

Full installation: permits, site prep, skilled trade labor, equipment, and structural warranty.

Estimated Sweat Equity
~$1,187

Average trade labor savings if executed as a skilled DIY homeowner project.

NEC Feeder Ampacity & Circular Mil Selection

Rendering formula...

100A Subpanel Wire Size for a 75 ft Aluminum Run

  1. Starting size: 1 AWG aluminum (the smallest aluminum conductor commonly rated for 100 A at 75°C).
  2. Voltage drop = 2 × 75 ft × 21.2 × 100 A ÷ 83,690 cmil = 1.58% of 240 V.
  3. That is within our 3% target, so 1 AWG works for this distance.
  4. 4-wire feed: 2 hots, 1 insulated neutral, 1 equipment ground.
Tip: Voltage drop is checked at the full 100 A. Have a licensed electrician confirm the wire type, conduit size and grounding against the code your area has adopted.

Quick Reference Sizing & Coverage Table

Standard commercial specifications and pre-calculated project benchmarks.

Feeder RunCopper (drop at 100 A)Aluminum (drop at 100 A)TargetInstalled Estimate
50 ft3 AWG (1.02%)1 AWG (1.06%)≤ 3%$1,300 – $2,050
100 ft3 AWG (2.04%)1 AWG (2.11%)≤ 3%$1,750 – $2,700
150 ft2 AWG (2.43%)1/0 AWG (2.51%)≤ 3%$2,605 – $3,935
200 ft1 AWG (2.57%)2/0 AWG (2.65%)≤ 3%$3,730 – $5,560
NFPA 70 (NEC) Table 310.16 ampacity and Chapter 9 Table 8 conductor properties

Have an Electrician Confirm the Design

The calculator starts from the smallest copper or aluminum conductor commonly rated for 100 A at 75°C and steps up until voltage drop at 100 A is 3% or less. A subpanel is fed with two hots, an insulated neutral and an equipment ground, with neutral and ground kept separate. Detached buildings have extra grounding rules, and wire type, conduit size and breaker ratings must match the code your area has adopted.

How to use the subpanel wire size calculator

  1. Measure the wire run from the main panel to the subpanel, following the actual route, in feet.
  2. Pick copper or aluminum conductors.
  3. Read the recommended size and its voltage drop. Have a licensed electrician confirm the wire type, conduit and grounding.

What size wire do I need for a 100 amp subpanel?

Our calculator starts with the smallest wire commonly rated for 100 amps at 75°C, 3 AWG copper or 1 AWG aluminum, then checks voltage drop at the full 100 amps. If the drop is over 3%, it moves up one size at a time.

Run lengthCopperAluminum
50 ft3 AWG (1.02% drop)1 AWG (1.06% drop)
100 ft3 AWG (2.04%)1 AWG (2.11%)
150 ft2 AWG (2.43%)1/0 AWG (2.51%)
200 ft1 AWG (2.57%)2/0 AWG (2.65%)

How do you calculate voltage drop for a subpanel?

Voltage drop = 2 × length × K × amps ÷ wire area in circular mils, where K is about 12.9 for copper and 21.2 for aluminum. For 180 ft of 1 AWG aluminum at 100 amps: 2 × 180 × 21.2 × 100 ÷ 83,690 = 9.1 volts, or 3.80% of 240 volts. That's over 3%, so the calculator moves up to 2/0 aluminum, at 2.39%.

Is 3% voltage drop a code requirement?

No. The NEC mentions 3% for feeders and 5% in total only in informational notes, which aren't enforceable. They're widely used as a design target because too much drop makes motors and tools run poorly. Our calculator uses 3% at the full 100 amps, which is on the cautious side.

Frequently asked questions

Copper or aluminum for a subpanel feeder?

Aluminum is cheaper and lighter but needs a larger size for the same current, as the table shows. Both work when the terminals are rated for the conductor and the connections are made to the manufacturer's torque specs.

What does it cost to add a 100 amp subpanel?

Our calculator estimates $1,750 to $2,700 installed for a 100 ft run, rising to $3,730 to $5,560 for 200 ft, where heavier wire is needed. Trenching and permit fees vary a lot by site.

Does a subpanel need four wires?

Yes. A subpanel is fed with two hot conductors, an insulated neutral and an equipment ground, and the neutral and ground are kept separate at the subpanel. Detached garages and sheds have extra grounding rules, so check with your inspector.