NEC 80% Continuous Rule & Voltage Drop Equation
NEC Article 625 Compliance Math for 48A EVSE over 60 Feet
- NEC Continuous Duty Calculation: 48A charging load × 125% continuous factor = 60A required circuit ampacity.
- Overcurrent Protection: Standard commercial double-pole breaker rounded up = 60 Amps.
- Voltage Drop Calculation: 2 × 60' × 48A × 0.4916158536585366 Ω/kft ÷ 1000 = 2.83V (1.18% drop on 240V).
- Voltage drop: 1.18% is within the common 3% design target (an informational note in the NEC, not a requirement).