NEC 80% Continuous Rule & Voltage Drop Equation
NEC Article 625 Compliance Math for 48A EVSE over 60 Feet
- NEC Continuous Duty Calculation: 48A charging load Γ 125% continuous factor = 60A required circuit ampacity.
- Overcurrent Protection: Standard commercial double-pole breaker rounded up = 60 Amps.
- Voltage Drop Calculation: 2 Γ 60' Γ 48A Γ 0.491 Ξ©/kft Γ· 1000 = 2.83V (1.18% drop on 240V).
- Compliance Check: 1.18% is safely below the NEC 3% branch circuit drop recommendation.